The Mitsubishi Electric ME96SSRB-MB (Model: ME96SSRB-MB) is a next-generation “Version B” electronic multi-measuring instrument designed for industrial and commercial power monitoring systems. Part of the renowned Super-S series, this 96×96 mm digital panel meter replaces multiple analog devices, offering high visibility and precision measurement for single-phase and three-phase electrical networks .
With a 55% reduction in unit depth compared to previous models, the ME96SSRB-MB fits seamlessly into new panels or retrofit projects. It supports up to 300 measured variables, including Voltage (V), Current (A), Power (W, var, VA), Frequency (Hz), Harmonics (up to 19th degree), and Energy (Wh) with IEC Class 0.5S accuracy .
Key Features & Benefits
1. High-Precision Measurement (Class 0.5S)
The ME96SSRB-MB provides certified revenue-grade energy accuracy. It complies with IEC 62053-22 Class 0.5S for active power (Wh) and IEC 62053-24 Class 1S for reactive power (varh) .
-
Accuracy Example: V, A, DA: ±0.2%; W, PF: ±0.5%; Hz: ±0.1%.
2. Advanced Communication & Networking
Standard MODBUS RTU (RS-485) communication allows seamless integration into Building Management Systems (BMS) and SCADA platforms .
-
Expandable: Supports optional plug-in modules for CC-Link (Ver 1.10/2.00) and MODBUS TCP (Ethernet) .
3. Built-in Data Logging & SD Backup
Unlike standard meters, the ME96SSRB-MB features a built-in logging function.
-
Data Security: An optional SD card backup module (ME-0000BU-SS96) retains valuable power data even during network communication failures, ensuring no data loss .
4. User-Friendly Interface & Installation
-
Display: Large backlit LCD supports 4-digit x 3 lines (or 6-digit x 1 line) for simultaneous viewing of up to 4 measurement types .
-
Compact Depth: 90mm depth allows installation in shallow enclosures.
-
Wiring Check: Built-in incorrect wiring determination pattern display prevents costly installation errors .
Technical Specifications
| Specification | Details |
|---|---|
| Model | ME96SSRB-MB |
| Mounting Dimensions | 96mm (H) x 96mm (W) x 90mm (D) |
| Weight | Approx. 0.5 kg |
| Primary Circuit Voltage | 3P4W: 277/480V AC; 3P3W/1P3W: 220/440V; 1P2W: 220/440V |
| Primary Current (CT) | 1A or 5A |
| Communication Standard | MODBUS RTU (Standard). Options: CC-Link, MODBUS TCP |
| Operating Temperature | -5°C to +55°C (Avg. 35°C or less) |
| Standards & Approvals | CE (EMC/LVD/RoHS), cURus, FCC, KC, UKCA |
Applications
-
Factory Automation (FA): Monitoring power consumption of production lines.
-
Building Management: HVAC efficiency tracking and lighting control.
-
Power Receiving/Substations: Voltage/Current monitoring via VT/CT secondary sides .
-
Data Centers: PUE optimization and energy visualization.